chase nipple | Electrician Talk

    https://www.electriciantalk.com/threads/chase-nipple.59676/
    Yes, under chase nipples it says to go to conduit fittings but they don't mention chase nipple (that name) in that section. I will add that some of the cmp members still consider the fitting to follow the rules of raceways for fill etc. If I install 5 18" nipples together I will have a 90" section of raceway and it is required to follow the rules.

Chase nipples | Mike Holt's Forum

    https://forums.mikeholt.com/threads/chase-nipples.115760/
    Used 3-2" chase nipples to feed branch circuits. Used center chase nipple for about 15 neutrals because of proximity to neutral bar. AHJ said I need to splice neutrals and pull them through with other conductors. 300.3 B applies if a chase nipple is considered and raceway. Wondering how it falls in application. infinity Moderator Staff member

Chase nipple | Mike Holt's Forum

    https://forums.mikeholt.com/threads/chase-nipple.103041/
    Chase nipples are listed as fittings, not raceways. don_resqcapt19 Moderator Staff member Location Illinois Occupation retired electrician Apr 9, 2013 #6 mjf said: I would think it is a tubing nipple not exceeding 24" Tubing is not threaded. kwired …

Chase Nipple Definition - Electrician's Slang

    http://www.electricalslang.com/Slang/chase%20nipple
    Chase Nipple Top Definition This fitting connects one electrical product to another through a knockout ranging from 3/8" to 6". It functions like a nipple except it is formed with a flat locknut affixed at one end. You'd use it to connect fixtures together to form continuous runs, connect metal boxes together, etc.

Chase Nipples | McMaster-Carr

    https://www.mcmaster.com/chase-nipples
    NPSM male × flanged end male straight adapters are also known as conduit nipples, chase nipples, and box adapters. The flange installs through a knockout from inside an outlet box or enclosure. Use with a locknut (not included) to create a short raceway between boxes or enclosures. For technical drawings and 3-D models, click on a part number.

Knowledge Beats Experience - Electrical Contractor Magazine

    https://www.ecmag.com/section/codes-standards/knowledge-beats-experience
    Over the years, many designers, installers and inspectors have interpreted 344.130 as classifying short lengths of raceways as 10 feet or less in length. However, it always is up to the inspector to make the final determination on what is considered a raceway, nipple or sleeve. EC

Do You Make This Mistake? Elbows, Couplings and Nipples Are

    https://www.wheatland.com/archives/60
    In this case “associated coupling” is the one listed to the raceways article and the “appropriate fittings” are those other than elbows, couplings and nipples listed to the raceway article. If “appropriate fittings” where used instead of “associated fittings” is may reduce the confusion.

Halex 1/2 in. Rigid Conduit Chase Nipples (100-Pack) 07005B

    https://www.homedepot.com/p/1-2-in-Rigid-Conduit-Chase-Nipples-100-Pack-07005B/202241109
    Terminate threaded conduit or provide a short raceway with the 1/2 in. Rigid Conduit Chase Nipples (100-Pack). These chase nipples are made of die-cast zinc and are ideal for use indoors or outdoors. These chase nipples meet UL and CSA requirements. Use with a rigid coupling to terminate threaded conduit to a knockout box or enclosure

What are the requirements for NM-cables entering an electric panel box?

    https://www.howtolookatahouse.com/Blog/Entries/2018/7/what-are-the-requirements-for-nm-cables-entering-an-electric-panel-box.html
    A fitting is installed at each end of the raceway to avoid abrasion of the cable jacket and fitting remain accessible after installation. The raceway is sealed at the outer end. The cable sheathing is continuous through the raceway and extends a minimum of 1/4” into box enclosure. The raceway is securely fastened at outer end.

Chase Nipples - Lumen

    https://www.lumen.ca/en/products/11-conduit-raceway-strut/03-conduit-fittings/02-metallic-conduit-fittings/12-rigid-conduit-fittings/10-nipples/01-chase-nipples
    Chase Nipple 17 Insulated Chase Nipple 8 Non-Insulated Chase Nipple 6 Chase Conduit Nipple 5. Thread Length. 16.51 mm 2 24.38 mm 2 8.63 mm 2 1-1/16 in 1 1-13/64 in 1 1-23/64 in 1 1-3/64 in 1 1-5/16 in 1 1-5/64 in 1 13.49 mm 1. 13/16 in 1 15 mm 1 17/32 in 1 19.05 mm 1 19.83 mm 1 21/32 in 1 29.97 mm 1 29/64 in 1 33/64 in 1 35/64 in 1 5/8 in 1 57 ...